ELECTRIC INVERTER,S ACCELERATION/DECELERATION TIME SETTING UNIT , ACCELERATION/DECELERATION TIME SWITCHING FREQUENCY. AND . S-CURVE CHARACTERISTIC TIME AT ACCELERATION START AND END.

ACCELERATION/DECELERATION TIME SETTING UNIT.

the acceleration time when multi function input emergency stop is on.0:unit:0.01 second 1:unit:0.1 second.
note:to set more precisely the acceleration time,please set c 1_10 to be 0. but the setting range in narrow.





ACCELERATION/DECELERATION TIME SWITCHING FREQUENCY.

set the frequency for automatic acceleration/switching below set frequency acceleration/deceleration time 4.above set frequency.acceleration/deceleration time 1 
note:please set the frequency point in the situation where automatic switching of accelerating/deceleration is needed.if the acceleration/deceleration time 
selector 1 and 2 are input via the multi function inputs,they will have priority.

S-CURVE CHARACTERISTIC TIME AT ACCELERATION START AND END.

c 2-01 s-curve characteristic time at acceleration start setting range is 0.0~2.50 and factory setting is 0.20.
c 2-02 s-curve characteristic time at acceleration end setting range is 0.00~2.50 and factory setting is 0.20.
the s-curve characteristic is set in unit of second.

note:

using the s-curve characteristic function for acceleration and deceleration can reduce shock to the machinery when stopping and starting. with the inverter s-curve characteristic times can be set respectively for beginning acceleration ending acceleration beginning deceleration,and ending deceleration. when the s-curve characteristic time is set the acceleration and deceleration times will be lengthened as follows, acceleration time= selected acceleration time + (s-curve at beginning of acceleration + s-curve at end of acceleration)/2 . deceleration time =selected deceleration