PID OFFSET ADJUSTMENT AND PID PRIMARY DELAY TIME CONSTANT.



PID OFFSET ADJUSTMENT.

it is used to set the offset of pid control in unit of % with max.output frequency taken as 100%.
note:
it is content to adjust the pid control offset.if both the target value and the feedback value are set to zero,adjust the inverter's output frequency to zero.

 PID PRIMARY DELAY TIME CONSTANT:

content b5_08 is the low pass filter setting for pid control outputs.and it is in unit of second.
note:
please set the low pass filter time content of pid control output.there is no need to change the default setting normally.if the viscus friction of the mechanical system is high,or if the rigidity is low,causing the mechanical system to oscillate, increase te setting so that it is higher than the oscillation frequency period.this will decrease the responsiveness,but it will prevent the oscillation.