TORQUE COMPENSATION GAIN AND TORQUE COMPENSATION TIME CONSTANT.


TORQUE COMPENSATION GAIN.

TORQUE COMPENSATION GAIN IS SET IN UNIT OF MULTIPLE DO NOT ADJUST THE SETTING OF THIS CONSTANT FOR OPEN LOOP VECTOR CONTROL .

NOTE:
THIS CONSTANT CAN BE CHANGED DURING OPERATION  BUT NORMALLY NO ADJUSTMENT ARE REQUIRED . WHEN THE CABLE IS LONG INCREASE THE SET VALUE . WHEN THE MOTOR CAPACITY IS SMALLER THAN THE INVERTER CAPACITY (MAX APPLICABLE MOTOR CAPACITY ) INCREASE THE SET VALUES . WHEN THE MOTOR IS OSCILLATING DECREASE THE SET VALUES. ADJUST THE OUTPUT CURRENT AT LOW SPREED TO BE LOWER THAN THE INVERTERS RATED OUTPUT CURRENT RANGE.







 TORQUE COMPENSATION TIME CONSTANT.

THE TORQUE COMPENSATION,S PRIMARY TIME DELAY IN UNITS OF MS .

NOTE:
THE TORQUE COMPENSATION TIME CONSTANT DOSE NOT NORMALLY NEED TO BE ADJUSTED  BUT MAKE ADJUSTMENTS IN THE FOLLOWING CASES . IF THE MOTOR GENERATES IF THE MOTOR GENERATES EXCESSIVE OSCILLATION RAISE THE SETTING . IF MOTOR RESPONSIVENESS IS LOW LOWER THE SETTING.