INVERTER,S SPEED LIMIT BIAS(d 5-0 5)



it is used to set the speed limit bias in unit of 100 % with max , output frequency take as 100%.
setting range is 0~120
factory setting is 10

NOTE:
the speed limit bias can be used to adjust the margins of the speed limit , when the speed limit bias is used , it is possible to set the same speed limit value in both the forward and reverse directions.
set the speed limit bias as a percentage of the maximum output frequency . (the max .frequency is 100%), for example  the following settings establish speed limits of 50% of the maximum output frequency in both the forward and reverse directions. speed limit bias setting  50%(d 5-0 5=50).
when a forward speed limit and a speed limit bias have been set the speed range of the torque control is from the - speed limit bias setting to the speed limit setting + speed limit bias setting.in effect the speed limit range is extended by the speed limit bias in both the forward and reverse directions. 