INTEGRAL VALUE DURING ACCEL/DECEL ENABLE /DISABLE AND OVERSPEED/EXCESSIVE SPEED OF INVERTER.





INTEGRAL VALUE DURING ACCEL/DECEL ENABLE /DISABLE.

Enable /disable integral value during ace/decal , 0: disable (the integral function is not used while accelerating or decelerating : it is used at constant speed). 1: enabled (the integral function is used at all times),
note: when v/f control with pg feedback is used integral control during acceleration and deceleration can be enabled or disabled with f 1-0 7, set f i-0 7 to 1 , (integral control enabled) if you want to keep the motor speed as close to the frequency reference as possible during acceleration and deceleration . set f 1-0 7 to  0,(integral control disabled) if you want to prevent the occurrence of overshooting / undershooting .

OVERSPEED/EXCESSIVE SPEED

To set the detection method of over speed ( os) .
note: when frequency exceeds the value set in f1-08 (set in unit of 1%with the maximum output frequency taken as 100 %) and it lasts more than f1-09 (diction time seconds) the over speed will be detected.
detection method for over speed deviation .
note: constant fi-10 sets the pg speed deviation detection level as a percentage of the maximum output frequency . constant f1-11  sets the length of time in seconds that the difference between the motor speed and reference speed must exceed the pg speed deviation detection level in order to detect a pg speed deviation.