MOTOR RATED CURRENT ; MOTOR RATED SLIP ; MOTOR NO LOAD CURRENT ; NUMBER OF MOTOR POLES AND MOTOR LINE TO LINE RESISTANCE.




MOTOR RATED CURRENT .

to set the motor's rated current in unit of a .
note ;please set it to be the rated current on the motor's name plate.

MOTOR RATED SLIP.

to set the motor's rated slip in unit of Hz.
note;it is the reference value of the motor;s slip . the factory setting depends on the inverter;s capacity . to calculate the motor;s rated slip according to the value on the motors name plate and set the value motor;s rated slip= motor;s rated frequency - rated speed  x the numbers of motor /120.

MOTOR NO LOAD CURRENT .

to set the motor;s current at zero  load in unit of a
note; the reference value of motor;s slip . the factory setting depends on the inverter;s capacity .please set the rated voltage and the current of the motor at the zero load and rated frequency , if there are no marks on motor;s nameplate , please inquire from the factory .

NUMBER OF MOTOR POLES .

to set the number of the motor;s poles .
note; set the value according to the record on the motor,s nameplate .

MOTOR LINE TO LINE RESISTANCE .

to set the value in unit of ohms.
note;it is the  reference value of motor,s torque compensation . the factory setting depends on the inverter,s capacity please set the motor,s line to line resistance (u v v w w u) if there is no cord in the motor,s nameplate please inquire from the manufacture.