440 VOLT THREE PHASE INVERTER,S SIGNAL LEVEL SELECTION (TERMINAL 14 )









Signal level selection of multifunction analogy terminal  14 
0: 0~+ 10 volt please make sure to cut off the overline 1
1: 0 ~+_10 volt please make sure to cut off the overline 1
2: 4 ~ +_20 ma  ( 10 bit input )
frequency (current ) it is effective when b1 _ 01 (frequency command selection ) is set to be 1
signal level to set frequency command (current )signal .

Note of setting


Setting value
content
0
0~+10v input  (10 bit input )
1
0~+_10v input (when the voltage is minus ,it will be the operation command which has opposite operation to the operation of the given command )
2
4~20ma input

When used as input voltage terminal ( setting : 0 or  1 , please cut off the overline on the control plate  ( if not the resistor will be burned ) . when voltage input terminal and current input terminal input frequency command simultaneously their summation will be the ultimate command value , in the occasion where voltage terminal and current terminal are used in turn , please set one of the multifunction input ( h1_01 ~06 ) to be 1f and this multifunction input 1s in off status , the current terminal (14) ,s command will be effective as long as the command from the voltage terminal ( 13 ) is on  , when it is et as 1 ( 0~ +_ 10 volt  input ) it is necessary that h3_01 is 1 too (0~+_ 10 volt input )  